📋 Case Study

Wind Farm Grid Connection

Subsynchronous resonance (SSR) risk and weak-grid-induced control instability during low-load conditions

🏗️ Project Overview

350 MW offshore wind farm connecting via VSC-HVDC to 400 kV mainland grid

🎯 Challenge

Subsynchronous resonance (SSR) risk and weak-grid-induced control instability during low-load conditions

🔧 Design Approach

Tuned SSR filters, grid-forming converter control architecture, and coordinated DC voltage droop + AC frequency support

📐 Design Diagram

Wind Farm SSR Filter fₛₛᵣ = 32.7 Hz Grid-Forming Converter Weak Grid SCR = 1.8 Coordinated Control: DC Voltage Droop + AC Freq Support Challenge: Subsynchronous Resonance & Control Instability

AI-generated project design illustration

📐 Key Calculations

SSR Modal Frequency

f_ssr ≈ 1/(2π√(L_eq × C_turbine))
Result: 32.7 Hz
Within turbine shaft torsional mode range—requires mitigation

Short-Circuit Ratio (SCR)

SCR = S_sc / S_wind
Result: 1.8
Classified as 'weak grid'—dictates GFMI requirements

📊 Results

Zero SSR events over 2-year commissioning; achieved ±0.15 Hz frequency regulation within 1.2 s; passed all ENTSO-E Dynamic Performance Tests

💡 Lessons Learned

  • SCR < 2 mandates grid-forming capability—not just grid-following
  • SSR filter design must consider harmonic interaction with turbine controls
  • HVDC control loops require co-simulation with EMT models

Key Takeaways

  • 1SCR < 2 mandates grid-forming capability—not just grid-following
  • 2SSR filter design must consider harmonic interaction with turbine controls
  • 3HVDC control loops require co-simulation with EMT models