π Case Study
110 kV Substation Expansion Study
Voltage drop exceeding 5% at downstream feeders; insufficient reactive support during peak summer load
ποΈ Project Overview
Expansion of regional 110 kV GIS substation serving growing urban load center
π― Challenge
Voltage drop exceeding 5% at downstream feeders; insufficient reactive support during peak summer load
π§ Design Approach
Integrated VAR compensation via 12 MVAR STATCOM + revised tap settings on 110/33 kV transformers; updated Y-Bus with new feeder impedances
π Design Diagram
AI-generated project design illustration
π Key Calculations
Voltage Profile Sensitivity (dV/dQ)
βV_i/βQ_j = Re(Yβ»ΒΉ)_ij
Result: -0.018 p.u./MVAR
Guided STATCOM placement at weakest bus (Bus #42)
Transformer Tap Optimization
V_out = V_in Γ (N_tap / N_nom)
Result: 1.025 pu tap ratio selected
Restored 33 kV bus voltage to 1.002 p.u. under peak load
π Results
Voltage deviation reduced from β6.2% to +0.8%; transformer loading decreased by 14%; STATCOM utilization < 65% across all scenariosπ‘ Lessons Learned
- β’STATCOM location must be validated using Q-V curvesβnot just voltage magnitude
- β’Tap scheduling requires co-optimization with capacitor banks
β Key Takeaways
- 1STATCOM location must be validated using Q-V curvesβnot just voltage magnitude
- 2Tap scheduling requires co-optimization with capacitor banks
π Prerequisites
Understand these before this topic
π Engineering Applications
See how this applies across industries